Measuring Principle | Hydrostatic | |
Characteristic |
Pressure transmitter for pressure or hydrostatic level measurement with flush mounted metallic CONTITE measuring cell: - hermetically welded - absolute condensation tight - climate-resitant - long-term stable - Lowest temperature influences Cable version with suspension clamp |
|
Supply voltage |
4...20mA HART 10,5...45V DC (Non Ex): Ex ia: 10,5...30V DC PROFIBUS PA: 9...32 V DC (Non Ex) FOUNDATION Fieldbus: 9...32 V DC (Non Ex) |
|
Reference Accuracy |
Standard 0,2% Optional 0,1% |
|
Long term stability | 0,05% of URL/year | |
Process temperature |
PE cable: -10°C…70°C / 14°F…158°F FEP cable: -10°C…80°C / 14°F…176°F |
|
Ambient temperature |
-40°C...85°C (-40°F...185°F) |
|
Measuring cell |
100mbar...10bar (1.5psi...150psi) |
|
Smallest calibratable span | 10 mbar (1.45 psi) | |
Vacuum resistance | 0 mbar abs. | |
Max. Turn down | 100:1 | |
Max. overpressure limit | 40 bar (600 psi) | |
Process connection | Mounting clamp | |
Material process membrane |
316L, AlloyC, Gold-Rhodium PE, FEP |
|
Material gasket | Viton, EPDM, Kalrez, none | |
Fill fluid |
Inert oil, Synthetic oil |
|
Material housing | 316L, Die-cast aluminum | |
Output |
4...20 mA HART PROFIBUS PA FOUNDATION Fieldbus |
|
Certificates / Approvals |
ATEX, FM, CSA, CSA C/US, IEC Ex, NEPSI SIL EN10204-3.1 NACE GL/ ABS/ LR/ BV/ DNV Marine KTW/ NSF Drinking water |
|
Options |
Initial device settings Overvoltage protection |
|
Specialities |
Modularity to differential pressure and process pressure devices (replacable display, universal electronics) Diagnostic functions Hermetically sealed Contite measuring cell (condensate-resistant and climatic-proofed) |
|
Application limits | If pressurized, usage of two pressure transmitters to measure the differential pressure (electronic dP) Observe ratio head pressure : hydrostatic pressure |